Send Message
Home News

Low-voltage Power Supply Systems

Company News
Low-voltage Power Supply Systems
Latest company news about Low-voltage Power Supply Systems

IEC terminology

 

International standard IEC 60364 distinguishes three families of earthing arrangements, using the two-letter codes TN, TT, and IT.

 

The first letter indicates the connection between earth and the power-supply equipment (generator or transformer):
"T" — Direct connection of a point with earth
"I" — No point is connected with earth, except perhaps via high impedance.

 

The second letter indicates the connection between earth or network and the electrical device being supplied:
"T" — Earth connection is by a local direct connection to earth, usually via a ground rod.
"N" — the earth connection is supplied by the electricity supply network, either separately to the neutral conductor (TN-S), combined with the neutral conductor (TN-C), or both (TN-C-S). These are discussed below.

 

Types of TN networks

 

In a TN earthing system, one of the points in the generator or transformer is connected with earth, usually the star point in a three-phase system. The body of the electrical device is connected with earth via this earth connection at the transformer. This arrangement is a current standard for residential and industrial electric systems particularly in Europe.

 

The conductor that connects the exposed metallic parts of the consumer's electrical installation is called protective earth (PE; see also: Ground). The conductor that connects to the star point in a three-phase system, or that carries the return current in a single-phase system, is called neutral (N). Three variants of TN systems are distinguished:

 

TN−S
PE and N are separate conductors that are connected together only near the power source.

latest company news about Low-voltage Power Supply Systems  0

TN−C
A combined PEN conductor fulfills the functions of both a PE and an N conductor. (On 230/400 V systems normally only used for distribution networks)

latest company news about Low-voltage Power Supply Systems  1

TN−C−S
Part of the system uses a combined PEN conductor, which is at some point split up into separate PE and N lines. The combined PEN conductor typically occurs between the substation and the entry point into the building, and earth and neutral are separated in the service head. In the UK, this system is also known as protective multiple earthing (PME), because of the practice of connecting the combined neutral-and-earth conductor via the shortest practicable route to local earth rods at the source and at intervals along the distribution networks to each premises, to provide both system earthing and equipment earthing at each of these locations. Similar systems in Australia and New Zealand are designated as multiple earthed neutral (MEN) and, in North America, as multi-grounded neutral (MGN).

 

latest company news about Low-voltage Power Supply Systems  2

 

TT network

 

In a TT earthing system, the protective earth connection for the consumer is provided by a local earth electrode, and there is another independently installed at the generator. There is no 'earth wire' between the two. The fault loop impedance is higher, and unless the electrode impedance is very low indeed, a TT installation should always have an RCD (GFCI) as its first isolator.

latest company news about Low-voltage Power Supply Systems  3

IT network

 

In an IT network, the electrical distribution system has no connection to earth at all, or it has only a high-impedance connection.

latest company news about Low-voltage Power Supply Systems  4

 

Pub Time : 2021-08-16 14:13:44 >> News list
Contact Details
Britec Electric Co., Ltd.

Contact Person: Macy Jin

Tel: 0577-62605320

Fax: 86-577-61678078

Send your inquiry directly to us